IS 308: the Indian Standard for dissolved acetylene and what it requires
IS 308 : 2024 specifies dissolved acetylene by its impurities, not by an assay: 4 % total impurities insoluble in acetone, 0.02 % hydrogen sulphide, 0.01 % phosphine and 0.25 % moisture, all maxima. The cylinder, porous mass, colour, retest interval and safety code come from five further standards.
- Standard
- IS 308 : 2024
- What IS 308 specifies
- Four impurity maxima
- Phosphine and hydrogen sulphide, max
- PH₃ 0.01 %
- Cylinder standard
- IS 7312 : 2018
- Retest interval
- 2 years
On this page 7 sections
What IS 308 covers #
IS 308 : 2024, Dissolved Acetylene (Fourth Revision), is the Indian Standard that specifies acetylene as a product. It works by capping impurities, and this is the part most suppliers get wrong: IS 308 sets no minimum acetylene content at all. Its Table 1 is four impurity maxima and nothing else.
So "conforms to IS 308" is a statement about what is not in the cylinder. It promises nothing about how much acetylene is. KIGL's ≥ 98 % is KIGL's own fill specification, published as such on dissolved acetylene — not a requirement of the standard, and no supplier can claim it by citing IS 308.
It does not specify the cylinder, the porous mass, the solvent, the colour or the retest interval. Each of those has its own standard. That is the normal pattern across every Indian gas standard: one document for the product, several more for what it arrives in.
| Standard | What it governs |
|---|---|
| IS 308 | The gas — impurity limits only; it sets no minimum assay |
| IS 7312 : 2018 | The cylinder, its porous mass and acetone charge |
| IS 8433 | Two-yearly periodic inspection |
| IS 4379 | Maroon, the identifying colour |
| IS 14814 | Code of safety — handling, storage, use |
What IS 308 controls — and what it does not #
This is the part suppliers get wrong, and it is worth being precise about.
IS 308 sets no minimum acetylene assay. It does not say the gas must be 98 %, or 99 %, or any figure at all. What it does is cap what must not be in the gas: total impurities insoluble in acetone, sulphur compounds measured as hydrogen sulphide, phosphorus compounds measured as phosphine, and moisture.
So when a supplier tells you "98 %, as required by IS 308", they are quoting a number the standard does not contain. It may still be a perfectly good fill specification, but it is the supplier's, not the standard's, and you should ask which.
KIGL fills to ≥ 98 % as its own specification, and inside the IS 308 impurity limits. That is a commitment rather than a floor, which is the stronger of the two claims.
For the limits themselves, work from IS 308 directly. KIGL uses it to set its specification rather than republishing its tables here.
The impurities it limits #
The two that matter are phosphine (PH₃) and hydrogen sulphide (H₂S).
Both come from the calcium carbide itself, not from the process, so they are always present to some degree in generated acetylene and must be removed by purification. They attack downstream equipment and they affect flame chemistry.
More usefully for a buyer: their level is the clearest single measure of whether the purification train on the generating plant is being maintained. A plant with tired purifiers keeps producing gas that looks normal and quietly carries more of both into cylinders. The damage lands on the customer's equipment, which is why it goes unnoticed for so long.
IS 308 against IS 14814 #
These get confused, and the distinction is simple:
- IS 308 says what the gas must be.
- IS 14814 says what you must do with it — storage, handling, piping, purging, use.
Most buyers need both. Note that IS 14814:2023 supersedes the 2000 edition, which is still cited in a good deal of circulating material.
Why the retest interval is two years #
Every other compressed gas cylinder in the range is hydrostatically requalified every five years under IS 8451. Dissolved acetylene is inspected every two, under IS 8433.
The reason is that an acetylene cylinder is not simply a steel shell. It contains a porous mass charged with acetone, and the inspection has to assess the mass and the solvent as well as the metal: see why acetylene is dissolved in acetone.
A supplier who treats acetylene cylinders on a five-year cycle has misunderstood which standard applies to them.
What KIGL does with it #
Dissolved acetylene is filled at the Guwahati works to IS 308, into cylinders built and requalified to IS 7312 : 2018 and IS 8433, identified maroon under IS 4379.
KIGL also builds the plants that generate it, to IS 8471, which means the purification train that determines whether the gas meets IS 308 is equipment KIGL designs as well as operates. The full conformance register is on the standards hub.
IS 308 — frequently asked questions
What does IS 308 actually specify?
Four maxima, and nothing else: total impurities insoluble in acetone 4 percent by volume, sulphur compounds as H₂S 0.02 percent, phosphorus compounds as PH₃ 0.01 percent, and moisture 0.25 percent by mass. Note what is absent — IS 308 sets no minimum acetylene assay at all. It also does not specify the cylinder, the porous mass, the solvent, the colour or the retest interval; each of those has its own standard, which is the normal pattern across every Indian gas standard.
Why are phosphine and hydrogen sulphide the impurities that matter?
Because they come from the calcium carbide itself rather than from the process, so they are always present to some degree and must be removed by purification. They attack downstream equipment and affect flame chemistry, and their level is the clearest measure of whether the purification train on the generating plant is being properly maintained.
Is 98 % the purity KIGL supplies?
It is KIGL's own committed fill specification, not a figure from the standard: IS 308 : 2024 Table 1 sets four impurity maxima and no minimum assay. Higher purity is available against a specific enquiry, and separate high purity and ultra-high-purity grades exist for work that industrial acetylene cannot serve. The grade ladder is set out on the acetylene grades guide.
What is the difference between IS 308 and IS 14814?
IS 308 specifies the product. IS 14814 is the Code of Safety — how acetylene is handled, stored, piped and used. One tells you what the gas must be; the other tells you what you must do with it. Buyers usually need both, and the 2023 edition of IS 14814 supersedes the 2000 one.
Why is the retest interval two years rather than five?
Because a dissolved acetylene cylinder is not just a steel shell. It contains a porous mass charged with acetone, and both have to be assessed as well as the metal. IS 8433 governs that inspection. Compressed gases are inspected every five years under IS 8451; acetylene is the exception across the whole range.
Does KIGL manufacture to IS 308?
Yes. Dissolved acetylene is filled at the Guwahati works to IS 308, into cylinders built and requalified to IS 7312 : 2018 and IS 8433, identified maroon under IS 4379. The conformance register on the standards hub sets out what KIGL works to for each activity and at which works.
References
Bureau of Indian Standards.
- IS 8471:2003, First RevisionAcetylene generators — Requirements (2003)
- IS 8433:2017, Second RevisionPeriodic inspection and maintenance of dissolved acetylene gas cylinders — Code of practice (2017)
- IS 7312:2018, Third RevisionWelded and seamless steel dissolved acetylene gas cylinders — Specification (2018)
- IS 4379:2021, Second RevisionIdentification of the contents of industrial gas cylinders (2021)
- IS 14814:2023, First RevisionAcetylene — Code of safety (2023)
- IS 308:2024, Fourth RevisionDissolved acetylene (gas) — Specification (2024)