Guide

IS 308:2024 explained what the Indian specification for dissolved acetylene actually limits, how it is tested, and what changed in the fourth revision

IS 308:2024, the Indian Standard for dissolved acetylene, limits impurities insoluble in acetone to 4 percent by volume, H₂S to 0.02 percent, PH₃ to 0.01 percent and moisture to 0.25 percent by mass. It sets no purity percentage; the 99 percent figure belongs to IS 1040 carbide gas.

Vertical acetylene purifier vessel with its charging manway and gas inlet and outlet pipework
Edition
IS 308:2024
Phosphine limit
Phosphorus compounds as PH₃ not more than 0.01 percent by volume
Hydrogen sulphide limit
Sulphur compounds as H₂S not more than 0.02 percent by volume
Insoluble impurities
Total impurities insoluble in acetone not more than 4 percent by volume
Moisture
Not more than 0.25 percent by mass

IS 308:2024 is the Indian Standard that defines what a cylinder of dissolved acetylene must contain, and — just as importantly — what it must not. It is a short document with four numerical limits, a sampling scheme and a set of laboratory methods, and it is widely misquoted: the "99 percent purity" that Indian suppliers attach to it is not in it at all. This page explains the four limits, how each is tested, where the 2024 fourth revision differs from the 1988 third revision, and how the Indian specification sits against the European grade codes.

What IS 308 is, and who writes it

IS 308 was first published in 1953 and revised in 1962, 1977 and 1988; the fourth revision was issued in July 2024 by the Industrial Gases Sectional Committee, CHD 06, under the Chemical Division Council. Its scope is the requirements and methods of sampling and test for dissolved acetylene gas. Clause 4.1 describes the product: acetylene dissolved in acetone to IS 170, or another solvent, held in a homogeneous porous substance packed in a cylinder so that it is not deemed an explosive under the Explosives Act 1884. That last phrase matters, because Government of India notification GSR 625(E) of 7 August 1983 declares acetylene an explosive when liquid, under pressure or mixed with air or oxygen; the porous mass and solvent are what take the product out of that definition. The cylinder side of the specification is on the dissolved acetylene standards page.

The four limits

Characteristic (IS 308:2024 Table 1) Limit Test method
Total impurities insoluble in acetone, percent by volume, max 4 Annex B-3, acetone absorption
Sulphur compounds as H₂S, percent by volume, max 0.02 (200 ppm) Annex B-4, hypochlorite and barium sulphate
Phosphorus compounds as PH₃, percent by volume, max 0.01 (100 ppm) Annex B-5, hypochlorite and molybdate
Moisture, percent by mass, max 0.25 Annex B-6, calcium chloride U-tubes

There is no row for acetylene content. The standard limits what may be present besides acetylene, and leaves the balance implied. A fifth requirement applies only to acetylene for navigational illuminants: clause 4.4 caps chloro-compounds at 0.001 percent by volume, tested by Annex B-7, a survival from the era of acetylene-lit buoys and lighthouses.

Where the "99 percent" comes from

Table 3 of the 1987 edition of IS 1040, the calcium carbide standard, requires the gas evolved from carbide in the laboratory to contain at least 99.0 percent acetylene by volume, with up to 0.15 percent H₂S, 0.06 to 0.08 percent PH₃ depending on quality, 0.001 percent arsine and 0.10 percent ammonia. That is a description of raw generator gas from compliant carbide. IS 308 describes the gas after purification, in the cylinder. The two are written by different committees — IS 1040 by the inorganic chemicals committee, IS 308 by the industrial gases committee — on unrelated revision cycles, and they are structured differently: IS 1040 has a positive assay and IS 308 does not. Read together, they define the purification duty: compliant carbide may legally deliver 0.15 percent H₂S and up to 0.08 percent PH₃, and the cylinder may contain 0.02 and 0.01 percent respectively, so the purifier train has to bring both impurities down by a large factor. Phosphine is the harder of the two, because the lime slurry in the generator holds back most of the sulphur but very little of the phosphorus, leaving the purifier to remove it. Indian carbide is at the high end of the world phosphine range, which is the subject of the phosphine in Indian carbide page, and the equipment that does the removing is described under acetylene purification systems.

Sampling — two samples, both must pass

Clause 6.1 allows samples to be drawn from the filling rack during filling, or from 5 percent of the cylinders after blowing off about 15 percent of the gas in them. Clause 6.2 requires two separate samples from the rack, and clause 7 declares the lot conforming only if both samples satisfy every requirement. Before the laboratory tests, Annex B-2.2 purges the sample cylinder through a regulator at 0.2 kgf/cm², venting about one sixth of the contents, so that the gas analysed represents the bulk and not the vapour space, where insoluble gases concentrate above the solvent.

The test methods, in plain terms

Silver nitrate screening (Annex B-2)

Gas is released for 30 seconds at not more than 0.2 kgf/cm² gauge onto filter paper wetted with 0.1 percent silver nitrate. Brown or black colouration is a failure. It is a go/no-go test for phosphine and hydrogen sulphide together; it cannot separate them, and arsine also stains. The test and its sensitivities are explained on the silver nitrate test page.

Insoluble impurities (Annex B-3)

Exactly 100 ml of gas is measured in a burette and shaken with acetone, which dissolves the acetylene and leaves the air, nitrogen, hydrogen, methane and carbon monoxide. The residual volume is read after 30 seconds' drainage, the temperature recorded, and the observed percentage corrected by the Annex C table, which allows for the solubility of water vapour and acetylene in the system across seven temperature bands from 0–9 °C to 46–50 °C. At 21–30 °C an observed 4.00 percent corrects to 2.8 percent; at 46–50 °C the same reading corrects to 1.00 percent. Fresh acetone is used after ten determinations.

Sulphur compounds (Annex B-4)

Between 10 and 15 litres of gas are passed at 2 litres per hour through two scrubbers each holding 25 ml of sodium hypochlorite with 3 to 3.5 percent available chlorine, saturated with sodium bicarbonate. Hydrogen sulphide is oxidised to sulphate, precipitated with 10 percent barium chloride, digested 15 minutes, left 4 hours, filtered on a G4 crucible and dried to constant mass at 105 to 110 °C. One gram of barium sulphate is equivalent to 0.096 litre of H₂S at NTP, and the result is (A − B)/V × 19.2 percent by volume, where A and B are the sample and blank masses and V the gas volume. The gas meter must be accurate to 1 percent.

Phosphorus compounds (Annex B-5)

The same hypochlorite scrubbing oxidises phosphine to phosphate. The scrubber liquor is evaporated, baked for an hour, taken up in hot water and nitric acid, boiled with ammonium nitrate, and precipitated with ammonium molybdate at 70 ± 1 °C. The ammonium phosphomolybdate is filtered on 9 cm Whatman No. 1 paper, dissolved in standard 0.1 N sodium hydroxide and back-titrated with 0.1 N hydrochloric acid against phenolphthalein. One millilitre of normal NaOH is equivalent to 0.00097 litre of PH₃ at NTP; the result is 0.194 (A − B) N / V percent by volume.

Moisture (Annex B-6)

Two tared U-tubes of anhydrous calcium chloride in series absorb water from the gas. The train is purged at 5 to 6 litres per hour for one hour, gas passed at 4 to 5 litres per hour for about 30 minutes to condition, then for 5 to 6 hours for the determination. The gain in mass against the mass of acetylene passed (22.4 litres being 26.04 g) gives the percentage by mass. Note the unit: moisture is by mass, the three gas limits are by volume.

What the 2024 revision changed

The four Table 1 limits are the same figures as in the 1988 third revision. The revision restyles the document, incorporates the two amendments issued to the 1988 edition, and updates the referenced standards: acetone to IS 170:2020, nitric and hydrochloric acids to IS 264:2005 and IS 265:2021, rectified spirit to IS 323:2009, reagent water to IS 1070:2023, rounding to IS 2:2022, dangerous-goods marking to IS 1260 (Part 1) and classification to IS 1446:2002. It carries the ICS code 71.100.20 and may be marked with the Standard Mark under the BIS Act 2016.

Two things did not change and are worth knowing. Clause 5.1 still refers the cylinder design to Government of India Notification M-1268(1) of 9 January 1939, with modifications ordered by the Chief Inspector of Explosives, whereas IS 309:2023, IS 1747:2023 and IS 307:2024 cite the Gas Cylinders Rules 2016 and the SMPV Rules 2016. The governing cylinder instrument in India is Rule 37 of the Gas Cylinders Rules 2016 and IS 7312:2018, whatever IS 308's packing clause says. And the standard still cites the 1973 edition of the gas-industry glossary IS 7062, which BIS revised in 2024.

IS 308 against the European grade codes

Specification Basis PH₃ (and AsH₃) H₂S
IS 308:2024 Impurity limits, no assay 100 ppm by volume 200 ppm by volume
EIGA Doc 240 grade 1.8 (98 percent), illustrative Purity code 1,000 ppmv PH₃/H₂S/AsH₃ combined included
EIGA Doc 240 grade 2.5 (99.5 percent), illustrative Purity code below 50 ppmv below 50 ppmv
EIGA Doc 240 grade 2.6 (99.6 percent), illustrative Purity code below 5 ppmv below 5 ppmv

EIGA Doc 240 codes grade by the count of leading nines and the next digit, and warns that words such as "industrial" and "high purity" have no legal definition. It also records that purified acetylene in European practice is typically below 10 ppmv phosphine and 10 ppmv H₂S, and that targets of 1 ppmv are not uncommon. IS 308's limits are therefore a floor, not a description of good practice; a filler whose purifier is working will be well inside them. KIGL's ultra-high-purity acetylene is specified against an impurity table (PH₃ and H₂S each not more than 10 ppm, a KIGL specification) for that reason, and the grade vocabulary is set out under acetylene grades explained.

Rules that matter

What this means for you

  • Ask a supplier for an impurity table per filling lot, not a purity percentage. IS 308 has no purity percentage to quote.
  • "99 percent to IS" describes carbide gas at the generator (IS 1040), not cylinder gas.
  • The limits are 100 ppm PH₃, 200 ppm H₂S, 4 percent insolubles by volume and 0.25 percent moisture by mass; a good plant runs an order of magnitude below the first two.
  • Lot conformity needs two samples from the rack, both passing; a single silver nitrate paper is a screen, not a certificate.
  • Cylinder requirements come from the Gas Cylinders Rules 2016 Rule 37 and IS 7312:2018, not from IS 308's 1939 packing reference.

IS 308 — frequently asked questions

What purity does IS 308 require for dissolved acetylene?

None, as a percentage. IS 308:2024 Table 1 has no acetylene assay row. It limits impurities: 4 percent by volume of material insoluble in acetone, 0.02 percent H₂S, 0.01 percent PH₃ and 0.25 percent by mass moisture. The "99 percent acetylene" figure often quoted for Indian acetylene comes from IS 1040 Table 3, which describes the gas evolved from calcium carbide at the generator, not the gas in a filled cylinder.

What changed in IS 308:2024 compared with IS 308:1988?

The four Table 1 limits are unchanged. The fourth revision restyles the standard, updates the referenced standards (acetone to IS 170:2020, reagent water to IS 1070:2023, rounding to IS 2:2022) and incorporates Amendments 1 and 2 to the 1988 edition. It also still refers cylinder design to Government of India Notification M-1268(1) of 9 January 1939, while the other 2023–2024 gas specifications cite the Gas Cylinders Rules 2016.

How is phosphine measured under IS 308?

By Annex B-5: the gas is scrubbed through sodium hypochlorite, which oxidises phosphine to phosphate; the phosphate is precipitated as ammonium phosphomolybdate with ammonium molybdate reagent, the washed precipitate is dissolved in standard 0.1 N sodium hydroxide and back-titrated with 0.1 N hydrochloric acid. One millilitre of normal NaOH is equivalent to 0.00097 litre of PH₃ at NTP, and the result is 0.194 (A − B) N / V percent by volume.

How is hydrogen sulphide measured under IS 308?

By Annex B-4: 10 to 15 litres of gas pass at 2 litres per hour through two scrubbers each holding 25 ml of sodium hypochlorite with 3 to 3.5 percent available chlorine, which oxidises H₂S to sulphate. The sulphate is precipitated as barium sulphate, digested, filtered on a G4 crucible and dried at 105 to 110 °C. One gram of barium sulphate is equivalent to 0.096 litre of H₂S at NTP.

What is the silver nitrate test in IS 308?

Annex B-2 is a qualitative check: gas released for 30 seconds through a regulator set at not more than 0.2 kgf/cm² is directed at filter paper wetted with 0.1 percent silver nitrate solution. A brown or black stain means phosphine or hydrogen sulphide and the sample fails. Arsine also stains the paper, and the silver acetylide formed is explosive when dry, so the papers are destroyed in dilute acid.

What is the 4 percent insoluble-impurity limit?

Annex B-3 passes exactly 100 ml of the gas into acetone in a burette; acetylene dissolves and the gas that remains — air, nitrogen, hydrogen, methane, carbon monoxide — is read as the insoluble fraction, corrected by the Annex C table for the temperature-dependent solubility of water and acetylene. Not more than 4 percent by volume may remain. Fresh acetone is used after ten determinations.

How does IS 308 compare with the European acetylene specification?

EIGA Doc 240 codes grades by purity — 1.8 means 98 percent, 2.5 means 99.5 percent — with illustrative phosphine, arsine and H₂S limits of 1,000 ppmv for grade 1.8 and below 50 ppmv for grade 2.5. IS 308's 100 ppm PH₃ and 200 ppm H₂S sit between those, and EIGA states that terms like "industrial" and "high purity" have no legal definition, which is why a grade code or an impurity table is the only meaningful purity claim.

Is IS 308 certification mandatory?

Clause 5.3 says the gas may be marked with the Standard Mark under the BIS Act 2016, which is voluntary certification. What is mandatory is the licensing and cylinder regime under the Gas Cylinders Rules 2016 and the cylinder standard IS 7312:2018. A supplier quoting IS 308 is undertaking that each filling lot meets Table 1 on two separate samples.

References

  1. Bureau of Indian Standards. (1987). Calcium Carbide, Technical — Specification, Bureau of Indian Standards (superseded by IS 1040:2024) (IS 1040:1987, Third Revision).
  2. Bureau of Indian Standards. (2024). Dissolved Acetylene (Gas) — Specification (IS 308:2024, Fourth Revision).
  3. European Industrial Gases Association. (n.d.). Commodity Specification — Acetylene (EIGA Doc 240).
  4. Government of India. (2016). Gas Cylinders Rules, 2016 (G.S.R. 1081(E)). Petroleum and Explosives Safety Organisation.